Decision. No central air- or ground-source heat pump, and no separate
ducted heating system. Heating is delivered by the same reversible
split air-conditioning units that cool each apartment (units run in
heating mode in winter). The building stays fully electric; gas
combustion remains out of scope for Phase 1.
Provision so owners mount easily. The building must foresee
everything an owner needs to mount AC units after move-in without
chasing walls — the necessary number of indoor units per apartment, one
for each habitable room (living, every bedroom, kitchen), each with:
- power supply at the indoor-unit position,
- refrigerant line routing to the matching outdoor position,
- condensate drainage.
The per-room hookup schedule is detailed in APT-09; ENG-02 owns the
heating-strategy decision, APT-09 the per-apartment provisioning.
Outdoor units — facade-integrated enclosures. Provide dedicated
housings on the facade to conceal the outdoor condensers, so the units
don't disrupt the elevation:
- pre-fixed mounting points at each outdoor-unit position,
- the enclosure (louvered screen / recess) painted in the facade
colour so it reads as part of the building, not as bolted-on plant.
Final detailing with the architect, coordinated with the facade
vocabulary (BLD-05) and the loggia louvers (APT-03).